凈化車間、無塵車間工程設(shè)計、裝修、施工是得創(chuàng)凈化工程公司主要從事業(yè)務(wù),價格實惠!
您只需一個電話我們將提供最合適的產(chǎn)品,讓您花最少的錢,達(dá)到最好的效果
無塵車間五個等級.得創(chuàng)凈化工程專業(yè)從事無塵車間工程規(guī)劃,設(shè)計,施工一條路凈化工程公司,歡迎來電咨詢:027-82289886
基于≥0.5um粒徑的各國潔凈度等級近似對照表
個/M3≥0.5um |
ISO 14644-1(1999) |
US 209E(1992) |
US 209D(1988) |
EEC GGMP(1989) |
FRANCE AFNOR(1981) |
GERMANY VDI 2083(1990) |
JAPAN JAOA(1989) |
1 |
- |
- |
- |
- |
- |
- |
- |
3.5 |
2 |
- |
- |
- |
- |
0 |
2 |
10.0 |
- |
M1 |
- |
- |
- |
- |
- |
35.3 |
3 |
M1.5 |
1 |
- |
- |
1 |
3 |
100 |
- |
M2 |
- |
- |
- |
- |
- |
353 |
4 |
M2.5 |
10 |
- |
- |
2 |
4 |
1,000 |
- |
M3 |
- |
- |
- |
- |
- |
3,530 |
5 |
M3.5 |
100 |
A B |
4,000 |
3 |
5 |
10,000 |
- |
M4 |
- |
- |
- |
- |
- |
35,300 |
6 |
M4.5 |
1,000 |
1,000 |
- |
4 |
6 |
100,000 |
- |
M5 |
- |
- |
- |
- |
- |
353,000 |
7 |
M5.5 |
10,000 |
C |
400,000 |
5 |
7 |
1,000,000 |
- |
M6 |
- |
- |
- |
- |
- |
3,530,000 |
8 |
M6.5 |
100,000 |
D |
4,000,000 |
6 |
8 |
10,000,000 |
- |
M7 |
- |
- |
- |
- |
- |
無塵車間防火疏散標(biāo)準(zhǔn)
1、潔凈廠房耐火等級不低于二級。吊頂材料應(yīng)為非燃燒體,其耐火極限不應(yīng)小于0.25小時。
2、無塵車間一般生產(chǎn)車間的火災(zāi)危險性,可按附錄三進(jìn)行分類。
3.甲、乙類生產(chǎn)的潔凈廠房應(yīng)采用單層廠房。防火墻是最大的允許面積,單層廠房應(yīng)為3000平方米,多層廠房應(yīng)為2000平方米。
4.在甲、乙類生產(chǎn)環(huán)境中潔凈廠房設(shè)置在甲、乙類生產(chǎn)環(huán)境中,其天花板和墻板(含內(nèi)部填充物)應(yīng)為非燃燒體。
5、在防火區(qū)的綜合廠房內(nèi),應(yīng)在潔凈生產(chǎn)與一般生產(chǎn)區(qū)之間設(shè)置非燃燒體隔墻,并將其封閉至頂部。當(dāng)隔墻及其相應(yīng)屋面的耐火極限不小于1時,隔墻上門窗的耐火極限不小于0.6小時。非燃燒材料應(yīng)緊密填充穿過隔墻或屋面的管道周圍的間隙。
6、技術(shù)豎井的井壁應(yīng)為非燃燒體,其耐火極限不得小于1小時。井壁檢查門的耐火極限不得小于0.6小時;在每層或一層地板上,應(yīng)使用相當(dāng)于地板耐火極限的非燃燒體進(jìn)行水平防火分離;非燃燒材料應(yīng)通過水平防火分離管道周圍的間隙緊密填充。
7.無塵車間各生產(chǎn)層、各防火分區(qū)或各潔凈區(qū)的安全出口數(shù)量不得少于兩個。
無塵車間振動控制標(biāo)準(zhǔn)
對于無塵車間及周邊輔助站房內(nèi)有強(qiáng)烈振動的設(shè)備(包括水泵等),應(yīng)采取積極的隔振措施。
對于無塵車間內(nèi)外的各種振動源,應(yīng)測量其對無塵車間的綜合振動影響。如果受到條件的限制,也可以根據(jù)經(jīng)驗評估綜合振動的影響。應(yīng)比較精密設(shè)備和精密儀器的允許環(huán)境振動值,以確定對其采取必要的隔振措施。
精密設(shè)備和精密儀器的隔振措施應(yīng)考慮減少發(fā)生量,保持潔凈室合理的氣流組織。當(dāng)使用空氣彈簧隔振臺時,應(yīng)處理當(dāng)?shù)氐臍庠矗赃_(dá)到潔凈室的空氣潔凈度水平。